Csslr Plus overstrømningsventil ¾" lige Indstillingsområde 0,2 - 0,6 bar. Max tryk 10 bar. Max temperatur 110°C
FBAC4895-B52C-4E03-B099-A6A8F8B8017B Created with sketchtool. 706D6907-81E1-46A2-B8F9-7B702A1EF2C7 Created with sketchtool. 6A870209-E7F5-44F5-A66F-09E20C85A0DC Created with sketchtool. 0BB04D6C-A9AB-4913-BF4F-5A23954E68E1 Created with sketchtool. 501E26C7-66C1-4DAA-B740-6CFAF55A1B39 Created with sketchtool. C105F7D3-D5EE-43C9-9EE8-05CC42B296D4 Created with sketchtool. D94689D8-7CBB-41C8-AC06-F79D81FF82D5 Created with sketchtool. DA4C7ED9-2512-4D52-94F0-92800F2A6E04 Created with sketchtool. 42E133FD-828F-4CF4-A0BF-560014487A57 Created with sketchtool. F52D9745-4BFD-4506-BEEF-630FD09EF2D9 Created with sketchtool.
Fjernlager
Varen er på fjernlager, leveringstiden er 3-4 hverdager. Mere info

Frakt 25,00 - Bring - Hentes på Posten.

NOK 555,00
eksklusiv MVA 444,00
Totalt inkl. frakt 580,00
Solar Plus overstrømningsventil 3/4" lige

USV overstrømningsventil er en selvvirkende reguleringsventil til varmeanlæg.
USV ventilen anvendes til at opretholde en minimum gennemstrømning i anlægget.

Indstillingsområde 0,2 - 0,6 bar.
Max tryk 10 bar.
Max temperatur 110 grader.
Fremstillet i messing CW617

Relief valve for systems with automatic or manual shut-off elements on the
radiators (thermostatic valves, two-way zone valves). Female inlet connections,
Male union outlet. Body and cap of brass CW617N.
Adjustment : Position 0 = Fully open - Position 7 = Close to closing ?p =0.5 bar
Plastic knob. Max operating pressure : 6 bar.
Overpressure : 10 - 15%. Max operating temperature : 110°C

By-pass valve series USVR can be set in this way:
Thighten blocking screw (1) (see overall dimensions).
Set the USVR valve at the differential opening pressure ?P by turning regulation knob (2) (see overall dimensions).
The differential opening pressure DP shall exceed the user circuit load loss at rated discharge by approximately
20% in order that avoid valve opening be prevented. When the user circuits is completely closed, the USVR
valve shall be fully open.
Turn regulation knob anticlockwise untilscale (3) (see overall dimensions) indicates zero. Then proceed, turning
clockwise, to calibration setting at the number required. Each number from 0-7 revers to an USVR16 - USVR20
USVR25 - USVR32.
Once the correct setting is established, it can be fixed with the locking screw of the handwheel